Product Description
Therma-Flow® Freeze-Protected Emergency Shower & Eyewash Systems
Therma-Flow® systems are fully enclosed, heat-traced emergency shower and eyewash units engineered to prevent freezing in cold and hazardous environments. Each system is built to order and configurable to meet specific application requirements including electrical classification, safety components, alarms, and accessories.
Representative Model: TF35B4777200
Due to the wide range of available configurations, Therma-Flow® systems are not sold as fixed SKUs. Contact Encon to configure a unit based on your site requirements.
Key Features
- Freeze-protected design with electric heat tracing
- Maintains internal temperature above freezing
- Fully enclosed ABS cover system with removable sections
- ANSI/ISEA Z358.1 compliant emergency performance
- Configurable shower, eyewash, and drench hose options
- Available with alarms, lighting, and monitoring systems
- Designed for industrial and classified environments
- Field-serviceable components for simplified maintenance
How It Works
Therma-Flow® systems utilize self-regulating electric heat tracing combined with closed-cell insulation to protect internal piping and components from freezing. The system is enclosed in segmented ABS covers that seal out environmental exposure while allowing access for maintenance.
- Heat trace cable maintains internal piping temperature
- Insulation retains heat within the enclosure
- Sealed cover system prevents cold air intrusion
- System remains operational in extreme cold conditions
Configuration Options
Each Therma-Flow® system is built using a configurable model structure. Options are selected based on site conditions, hazard level, and operational requirements.
Electrical & Classification
- NEMA 4 configurations
- Class I, Division 2 rated options
- 120V and 240V systems available
Water Inlet Configurations
- Top or bottom inlet
- 1-1/4″ and 1-1/2″ connections
- Dual inlet configurations available
Safety System Configurations
- Shower and eyewash combinations
- Drench hose options
- 20 GPM and 30 GPM shower configurations
Lighting & Controls
- Area lights (side mount or top mount)
- Heat trace indicator lights
- Combined lighting configurations
Protection & Monitoring
- Freeze protection valves
- Scald protection valves
- Thermometer options
Alarm Systems
- Visual alarms
- Audible alarms (bell, horn, PulseTone™)
- Combined light and audible systems
Activation & Monitoring
- Flow switches (top or bottom connection)
- MAP® switch systems
- Remote monitoring capability
Additional Options
- Underground extensions
- Extended cable lengths
- Cover color options
Performance Specifications
Shower
- Minimum 20 GPM flow rate
- Full spray pattern coverage for emergency use
Eyewash
- Minimum 0.4 GPM flow rate
- Non-injurious, controlled flow pattern
Operation
- Activation in 1 second or less
- Simultaneous operation of components
Construction & Materials
- ABS protective outer covers
- Heat-traced internal piping
- Closed-cell insulation system
- Neoprene sealing strips with compression fit
- Corrosion-resistant internal components
Installation & Operation
- Floor-mounted unit with flange base
- Requires potable water supply
- Requires electrical connection for heat tracing
- Designed for two-point electrical connection
- Install per IOM guidelines for proper performance
Maintenance
- Weekly activation testing recommended
- Modular cover system allows easy access
- Field-repairable valves and components
- Replacement parts and kits available
Applications
- Oil and gas facilities
- Chemical processing plants
- Refineries
- Outdoor industrial sites
- Cold climate environments
- Hazardous and classified locations
Ordering Information
Therma-Flow® systems are built to order based on your application requirements. Due to the number of available configurations, orders must be placed through Encon directly.
Our team will assist in selecting the correct configuration based on your site conditions, hazard requirements, and compliance needs.
Specifications
Freeze Protection
Freeze Protection Valve, Heat Tracing
Scald Protection
Closed Cell Foam Insulation, High Limit Thermostat, In-Line Scald Protection Valve
Optional Electrical Class
NEMA 4
Certification Classes
CSA, FM, UL
Product Families
Therma-Flow Protected Showers
High Visibility Cover Options
Green, Orange, Yellow
Options Freeze Protected Showers
Alarm Lighting, Area Lighting, Audible Bell, Audible Horn, Audible Pulse Tone, Flow Switch, Heat Trace Indicator, In-Line Water Thermometer
Voltage Options Freeze Protected Showers
120V, 240V
Resources